SEIZED PUMPS? NOT A PROBLEM…

When this residential establishment encountered a burning issue within their chilled water cooling system, it was time to call out a specialist – and fast! Their two 15kw belt drive pumps were not only highly inefficient but were also posing a serious fire risk.

 

CHALLENGE

One of their pumps had completely seized up as it had burnt through the belt, and was now setting off the building’s fire alarm system. The fire brigade had already attended the site due to the alarm, but when the problem couldn’t be identified the Dura Pump team were called out to assess the issue.

 

SOLUTION

Our team found the root of the problem, the seized pump, and set about coming up with the best solution to get them up and running. They took down all the details and provided a quote to replace the belt drive pumps with direct drive centrifugal pumps with Danfoss inverters.

These new replacement pumps are 11kw and able to to withstand peak demand even in temperatures above 25 degrees. They also only require 7.5kw, which is half the power requirement of the original pumps!

The system now works on differential pressure transducers and the pump is able to monitor the demand and deliver the results to suit.

 

RESULTS

They now have a much more reliable pump system, and with the belts removed they have reduced their maintenance requirements and any potential fire hazards. In addition, the increased efficiency in their centrifugal pumps is sure to provide this happy customer with a fantastic payback!

< Back to Case Studies

Accreditations & Affiliations

About Us

Mission
Our mission is: To create flow the way you need it

Vision
We are driven by our vision, where we see: A world where pump reliability is paramount.

We see ourselves: Satisfying the pump user through effective and efficient fluid management

 

Useful Links

Contact

01604 648 800
mail@durapump.co.uk

Dura Pump Ltd
Boughton Fair Lane
Moulton
Northants
NN3 7RT

Latest News

Avoid heating system failure this winter

Avoid heating system failure this winter Winter is the worst time to experience a heating system failure. Here at Dura Pump, our team is focused...

Read more >

Are your cooling systems still running even though it’s winter?

ARE YOUR COOLING SYSTEMS STILL RUNNING EVEN THOUGH IT’S WINTER? It is surprising how many people don’t realise that the pumps in their cooling systems...

Read more >

© Copyright 2019 by Dura Pump. All rights reserved.