400 Litre Pressure Vessel Replacement for Data Centre
The Challenge
Replacing a failed vessel to restore system pressure stability
During a routine service visit, engineers found the site’s 400-litre pressure vessel solid sounding and full of water, a clear indicator of internal bladder or diaphragm failure. A failed pressure vessel can no longer absorb pressure fluctuations across the pump system, increasing the risk of pressure surges and additional stress on connected pumps and pipework. Replacement was recommended rather than repair.
The Solution
- Engineers attended site, safely isolated, drained down and removed the failed 400-litre vessel.
- A replacement 400-litre vessel was supplied and installed.
- Mechanical connections were carried out to reinstate the vessel within the pressurisation circuit.
- The vessel was charged and set to the correct operating pressure, then tested and commissioned.
The Outcome
System pressure stability was restored, removing the risk posed by the failed vessel to the wider pump circuit.
- Pressure fluctuation risk across the circuit was eliminated.
- Connected pumps and pipework were protected from the additional stress a failed vessel would otherwise cause
- A prompt diagnosis-to-replacement turnaround minimised the window of risk to the system.