The Challenge

A leading hospital in Warwickshire, serving hundreds of patients daily with 358 beds for emergency and elective services, had issues with failing main circulation pumps every 8 to 12 months. As a result, they had to be removed and overhauled.

These Low Temperature Hot Water (LTHW) pumps were operating outside of their designed duty which meant that they were cavitating. This caused the mechanical seal and bearings to fail prematurely. Ultimately, the pumps were not suited to the system requirements. The incorrect specification meant that these pumps had to run continuously at full speed to delivery sufficient heat around the system. For every month the existing heating pump system was operating, it was costing and extra £3,153 to run, compared to the correctly specified pump.

puzzle icon

The Solution


We recommended the correct pump specification together with inverters so that the new pumps could deliver to curve and flowrate. The new solution included:

  • Correctly specified pumps to match the required flow rate and pressure.
  • Variable speed inverters to adjust pump operation on actual demand rather than running continuously at full speed.
  • A future proof system, reducing long-term maintenance costs and extending equipment lifespan.

Technical Specification
To achieve maximum efficiency, we installed:

  • Lowara NSCS 150-250 – 30 kW end suction pumps.
  • Danfoss FC102 – 30 kW inverters for optimised energy consumption.
outcome icon

The Outcome

Our hospital customer now benefits from:

  • 40% energy savings – reducing annual electricity consumption by 94,608kWh.
  • Pumps that will only require an overhaul every 5 to 10 years (estimated).
  • Significant cost reduction – achieving an impressive 17-month payback period.
  • Reduced carbon footprint – contributing to the hospital’s sustainability goals.
  • Quieter operation – reducing plant room noise for a more comfortable working environment.
  • Long term security – new pumps with a 24-month warranty and a 10-year spare part guarantee.

By optimising their heating pump system, the hospital is now operating more sustainably, more efficiently and at lower costs. This ensures uninterrupted comfort for patients and staff.

Do you need a similar energy-saving and cost saving solution?

Contact us today to cut costs, boost efficiency and enhance reliability.
Follow us on LinkedIn to stay updated with all Dura Pump news!

Choosing Dura Pump means investing in reliability and safety for your facility. Talk to an expert about your needs

We’ve had great reviews

Clear, Consistent Communication

The communication from Dura Pump to the customer is very good. We knew what was happening with the repair every step of the way

Purchasing Manager

Outstanding Turnaround

We just wanted to feedback our grateful thanks to Chris and Phil for all their hard work yesterday in getting us up and running again. To turn us around from failure to full recovery in 4/5 hrs was nothing short of exceptional. Please pass on our gratitude to them both.

Operations Manager

Seamless End-to-End Service

Service and communication received from initial inspection and specification through to delivery and installation of our replacement system was seamless. Thank you.

Facilities Supervisor

Informative & Helpful Engineers

Your engineers are always informative and always let me know when they are on site. Always very helpful, always kept well informed, which makes such a difference!

Building Manager

Fast, Friendly & Efficient

Fast, efficient, friendly staff in sales, accounts and installation. Very happy.

Project Coordinator

Top-Quality Workmanship

Over the moon with the service and quality of work/engineers.

Maintenance Manager